ZHK 2000

produkte-ZHK-2000


Technical Specification

Technical Specification ZHK 2000

Housing assembled with self supporting modular panels with base frame integrated into the unit and aluminium profiles along the upper sides of the unit. Inside and outside walls completely smooth. The 50 mm thick double skin panel contains a glass fibre insulation, complying with fire protection class 0 of ISO 1182.2 an class A1 of DIN 4102. The fibre glass guarantees an optimal thermal and acoustic insulation. On the front sides of the inner panels there are centred holes at a distance of 152,5 mm each. Through these holes the panels are fixed to each other. In order to obtain a high stability of the structure, the inner panel has two bending on the outer side, allowing consequently an easy assembly of the outer panel skin. Additionally, the overlapping sheets on the angles are micro welded on each other. A quick assembly and disassembly of the outer panel skin is possible through the international patented snap-in-assembly construction with a special profile on the inner side of the outer panel skin. The air handling units are equipped with large dimensioned access doors (EU.T) in same thickness and execution as panel, door frame made of aluminium, special rubber seal with welded corners, adjustable hinges, safety locks with removable handles. The doors are foreseen for fan- filter- and humidifier section. Removable inspection panels (TRA) with patented service locks are foreseen for prefilters and antifrost frame sections and on request also for other sections. The execution is the same as the panel, door frame made of aluminium, rubber seal. With screws removable panels (TRA-E) are foreseen for electric heater section and on request for other sections. The execution is the same as the panel, door frame made of aluminium.


Certified data of AHU casing conform to EN 1886

 

  • Casing strength: class 2 A
  • Casing air leakage at –400 Pa: class A/ B*
  • Casing air leakage at +700 Pa: class A/ B*
  • Filter bypass leakage: class F9
  • Thermal transmittance: class T4
  • Thermal bridging factor: class TB3

* Class obtained with special hygienic sealant

  • Sound attenuation Rw (DIN 52210-03): 36 dB
  • Sound attenuation of the panel certified in compliance with EN 1886 and EN ISO 3744:

Frq. Hz 125 250 500 1000 2000 4000 8000
Okt. dB 13 21 26 27 27 31 36

  • Performance data certified in compliance with EN I 3053
  • Heat exchangers certified in compliance with EUROVENT Rating Standard 6/C/005/1997

Panel executions (Standard)

  • Inner skin: 1,00 mm galvanized sheet
  • Outer skin: 0,7 mm galvanized sheet with additional surface coating in blue plastic type B5V, thickness 200 m
  • Incombustible fibre glass insulation thickness  50 mm
  • calculated heat transfer coefficient  k = 0,59 W/m2K
  • Base frame made of galvanized sheet metal, hot dip galvanised or painted steel profiles for great units

Special materials

  • Stainless steel
  • Aluminium
  • Epoxy-Coating
  • Powder coating

Weatherproof execution (in addition to standard)

  • Weatherproof canopy
  • Additional sealing of the panels and watertight
  • Service doors

Hygienic execution (in addition to standard)

  • All components can be removed through large doors
  • Floor panel made as inclined drain pan
  • Inner panel connections sealed with special sealant, steam tight, resistant to all known disinfectants and cleaning agents

Industrial (in addition to standard)

  • Inner skin: 1,50 mm galvanized sheet
  • Outer skin: 1,0 mm galvanized sheet with additional surface coating in blue plastic type B5V, thickness 200 m
  • Sound attenuation Rw (DIN 52210-03): 41 dB
  • Sound attenuation of the panel certified in compliance with EN 1886 and EN ISO:

Frq. Hz 125 250 500 1000 2000 4000 8000
Okt. dB 14 25 28 27 29 31 34


ATEX
In compliance with 94/9EG / ATEX 100a
  • Modular units
    Personalized units for your requirements and special units

  • Standardized units
    Standard air units

  • Accessories
    ETA Matic, FilterSafe